Crestron CHV-TSTAT and CHV-THSTAT
Humidifier Related Joins (continued)
Signal Name
OUTDOOR_HUMID_F
REGULATION_HUMID_F
BUILT_IN_HUMID_F
REM1_HUMID_F
REM2_HUMID_F
HVAC Related Analog Joins
Signal Name
SETPOINT_1
SETPOINT_1_F
SETPOINT_2
SETPOINT_2_F
OUTDOOR_TEMP
OUTDOOR_TEMP_F
Operations and Installation Guide - DOC. 8163
Symbol
I/O
Both
Output
Both
Output
Advanced
Output
Advanced
Output
Advanced
Output
NOTE: All temperatures except for setpoint values are expressed in tenths of degrees.
For example: sending 703 means 70.3.
Symbol
I/O
Both
Input
Both
Output
Both
Input
Both
Output
Both
Input
Both
Output
Definition
Analog value that is output if a connected remote
temperature/humidity sensor is declared as "outdoor" Can
be used to distribute the reading to other thermostats for
display purposes
The "regulation" humidity that a thermostat is using, This
is the average of the humidity sensor inputs declared
"use" in set-up This output is only active when a
thermostat setup has humidity sensing capability, either
by being a CHV-THSTAT or a CHV-TSTAT with humidity
remote (Analog)
Humidity value of built-in sensor (Analog) Output will
send out the sensor values even if the sensor is declared,
"omit"
Humidity value of remote 1 sensor (Analog) Output will be
zero if the sensor is not installed Output will send out the
sensor values even if the sensor is declared "omit"
Humidity value of remote 2 sensor (Analog) Output will be
zero if the sensor is not installed Output will send out the
sensor values even if the sensor is declared "omit"
Definition
The primary setpoint value, in whole numbers, Example:
71 means the setpoint is 71 degrees, It is the value used
in heat, cool, and "aux heat only" modes, When operating
in auto mode, setpoint_1 can mean two things,
depending on setup, If the option "dual setpoint auto" is
Yes, then setpoint is the heat setpoint If No is selected,
then setpoint is the only setpoint (single-point auto only
has one setpoint)
Output of setpoint 1, in whole numbers
Secondary setpoint value, which is ONLY used as the
cooling setpoint in auto when "Dual setpoint auto" is
selected as Yes
Output of setpoint 2, in whole numbers
Input that allows the outdoor temperature value to be
retrieved from Cresnet for display on the "outdoor" page,
This value is ignored when a thermostat has a remote-
outdoor sensor connected to it Also used for balance
point action on heat pump systems, in 10ths of degrees
Output used for sending outdoor temperature to other
units It takes the value of remote sensors declared
"OD"(Outdoor) Output is zero if no remotes are declared
"OD", in 10ths of degrees
Thermostats: CHV-TSTAT and CHV-THSTAT • 29