Chapter 5
Troubleshooting the Cisco RPS
Table 5-1
Symptoms and Recommended Responses
Symptom
DC LED 1, 2, 3, or 4 is
amber.
Note
The DC LED is
always amber
for 10 to 15
seconds after
the DC output
module has
been connected
and the
external device
has been
powered on.
OL-3654-01
Description of Error
The cable connected to an
internal DC output module is
loose, or the internal DC output
module has failed.
If you are using a
Note
Cisco RPS with a
revision level lower
than Z3 with a Catalyst
3508G or a Catalyst
3548 XL switch, the
switch RPS LED and
the RPS DC LED of the
connector to the switch
might display amber
(normally indicating a
Cisco RPS
malfunction) even when
the Cisco RPS is
functioning properly.
The LEDs display
correctly for Cisco RPS
revision level Z3 or
later. The label on the
bottom of the
Cisco RPS shows the
revision level.
Cisco Redundant Power System Hardware Installation Guide
Corrective Action
The DC status LED numbers correspond
to the DC output connectors on the
Cisco RPS rear panel. Check the LEDs to
determine which connector is affected.
The following steps power down
Note
the external device if it is not
already down.
Disconnect the corresponding output
1.
cable from the external device. The
amber light goes off.
Ensure that the other end of the output
2.
cable is securely connected to the
Cisco RPS and that the connector is
fully seated.
Reconnect the output cable to the
3.
external device.
Ensure that the connector is fully
4.
seated and is attached securely to the
external device.
Wait 15 seconds. The LED is amber
5.
for 15 seconds and then is green.
If the failure persists, the DC output
module has failed, and the Cisco RPS
needs to be replaced. If there is an unused
DC output module, try switching to it as a
temporary solution.
Reading the LEDs
5-3