Jumper And Switch Settings - Daikin G-Series Service Manual

Inverter multi for 2 rooms
Hide thumbs Also See for G-Series:
Table of Contents

Advertisement

Field Settings

4.1.3 Jumper and Switch Settings

<Floor Standing Type>
<Floor / Ceiling Suspended Dual Type>
For the location of the jumper and the switch, refer to the following pages.
258
Jumper
(on indoor unit PCB)
JB
Fan speed setting
when compressor
stops for thermostat
OFF. (effective only
at cooling operation)
JC
Power failure
recovery function
Switch
(on indoor unit PCB)
SW2-4
Upward airflow limit
setting
Switch
(on indoor unit PCB)
SW2
Installation style
changeover
Wall mounted type: page 37, 39, 42
Floor Standing Type: page 49
Floor / Ceiling Suspended Dual Type: page 46
Duct connected type: page 44
Function
When connected
(factory set)
Fan speed setting ;
Remote controller
setting
Auto-restart
Function
OFF
(factory set)
Exposed or half
embedded
installation
Function
FLOOR
(factory set)
When installed as
the floor mounted
type
SiBE12-933_A
When cut
Fan speed setting; "0" (The fan
stops.)
The unit does not resume
operation after recovering from a
power failure. Timer settings are
cleared.
ON
Set the switch to ON position
when you install the indoor unit
embedded in the wall to avoid
condensation.
CEILING
When installed as the ceiling
suspended type
Trial Operation and Field Settings