Automatic Operation - Daikin G-Series Service Manual

Inverter multi for 2 rooms
Hide thumbs Also See for G-Series:
Table of Contents

Advertisement

Main Functions
1.7

Automatic Operation

Automatic Cooling / Heating Function (Heat Pump Only)
When the AUTO mode is selected with the remote controller, the microcomputer automatically
determines the operation mode from cooling and heating according to the room temperature
and setting temperature at the time of the operation startup, and automatically operates in that
mode.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature at the main unit setting temperature.
Detailed
1. Remote controller setting temperature is set as automatic cooling / heating setting
Explanation of
2. Main unit setting temperature equals remote controller setting temperature.
the Function
3. Operation ON / OFF point and mode switching point are as follows.
4. During initial operation
Ex: When the set point is 25°C
64
temperature (18 to 30°C).
(1) Heating → Cooling switching point:
Room temperature ≥ Main unit setting temperature +3.0 deg.
(2) Cooling → Heating switching point:
Room temperature < Main unit setting temperature –2.5 deg.
(3) Thermostat ON / OFF point is the same as the ON / OFF point of cooling or heating
operation.
Room temperature ≥ Remote controller setting temperature: Cooling operation
Room temperature < Remote controller setting temperature: Heating operation
Set point –2.0ºC
=Thermostat OFF
Set point –2.5ºC
Cooling Operation → 23°C: Thermostat OFF → 22°C: Switch to Heating Operation
Heating Operation → 27°C: Thermostat OFF → 28°C: Switch to Cooling Operation
Cooling Operation
Heating Operation
SiBE12-933_A
Set point +3.0ºC
Set point +2.0ºC
=Thermostat OFF
(R9417)
Function and Control