Compressor Lock - Daikin G-Series Service Manual

Inverter multi for 2 rooms
Hide thumbs Also See for G-Series:
Table of Contents

Advertisement

Troubleshooting
4.9

Compressor Lock

E6
Remote
Controller
Display
Method of
Judging from current waveform generated when high-frequency voltage is applied to the
Malfunction
compressor.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.14
Refer to P.219
186
The system is shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 11 minutes (normal)
Compressor locked
Disconnection of compressor harness
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Turn off the power. Disconnect the
harnesses U, V and W.
Check No. 14
Check with the inverter checker ( ∗ ).
Normal?
YES
Turn off the power and reconnect
the harnesses. Turn on the power
again and get the system restarted.
Emergency stop
without compressor
running?
NO
System shut down
after errors repeated
several times?
YES
∗ Inverter checker
Part No.: 1225477
NO
YES
NO
SiBE12-933_A
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
Replace the compressor.
Check the electronic
expansion valve.
Replace it as required.
Replace the compressor.
(R7172)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents