4.16 DC Voltage / DC Current Sensor Abnormality

H8
Remote
Controller
Display
Method of
DC voltage or DC current sensor system fault is identified based on the compressor operation
Malfunction
frequency and the input current detected by the product of DC current and DC voltage.
Detection
Malfunction
When the compressor operation frequency is more than 52 Hz
and when the DC current is less than 0.3 A or DC voltage is less than 50V.
Decision
Conditions
Supposed
Causes
Troubleshooting
Replace the outdoor unit PCB.
196
If this error repeats 4 times, the system is shut down.
The error counter is reset if this or any other error does not occur during the following 60-
minute compressor running time (total time).
Power transistor defective
Internal wiring broken or in poor contact
Reactor defective
Outdoor unit PCB defective
Refrigerant shortage
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.