Table 6-1 Temperature Sensors Thresholds - Kontron AT8060 User Manual

Single width atca compliant processor blade
Hide thumbs Also See for AT8060:
Table of Contents

Advertisement

IPMI non-recoverable / PICMG 3.0 critical/ telco critical:
Temperature has reached a destructive level. Device might be damaged.
Most ATCA chassis react to temperature events in the following manner: When a minor threshold is reached,
the shelf manager will incrementally increase airflow (fan speed) to bring the temperature below the crossed
threshold. When a major threshold is reached, the shelf manager will increase the fans to maximum speed.
When a critical threshold is reached, the shelf manager will shutdown the blade to prevent damage. The shelf
alarm panel, when available, can inform the operator with LEDs when an alarm (minor, major, critical) is
raised. Refer to your chassis documentation to adapt and optimize your temperature monitoring application
to chassis capabilities. See also System Airflow section for more information.
Below is the list of temperature sensors with their respective thresholds.
Table 6-1:Temperature Sensors Thresholds
Sensor ID
Minor
Temp -48V A Feed
N/A
Temp -48V B Feed
N/A
Temp Mez 12V Out
N/A
Temp CPU
+5°C
Temp Vcore0
-35°C
Temp Vcore1
-35°C
Temp VDDQ
-35°C
Temp IOH
+10°C
Temp ICH
+5°C
Temp Mngt Lan
+5°C
Temp BI Lan
+5°C
Temp FI Lan
+5°C
Temp IPMC
+5°C
Temp Bay Inlet
+5°C
Temp DIMM#1
5°C
(Channel 0, Dimm0)
Temp DIMM#2
5°C
(Channel 0, Dimm1)
Temp DIMM#3
5°C
(Channel1, Dimm0)
Temp DIMM#4
5°C
(Channel 1, Dimm1)
Temp DIMM#5
5°C
(Channel 2, Dimm0)
Temp DIMM#6
5°C
(Channel 2, Dimm1)
Temp DIMM#7
5°C
(Channel 3, Dimm0)
Temp DIMM#8
5°C
(Channel 3, Dimm1)
Lower Thresholds
Major
Critical
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
-40°C
-50°C
-40°C
-50°C
-40°C
-50°C
+5
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
0°C
-10°C
112
Thermal Considerations
Upper Thresholds
Minor
Major
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+77°C
TCC-5°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+85°C
+95°C
+90°C
+100°C
+90°C
+100°C
+90°C
+100°C
+90°C
+100°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
+75°C
+85°C
www.kontron.com
Critical
+110°C
+110°C
+110°C
+125°C
+95°C
+95°C
+95°C
+95°C
+105°C
+110°C
+110°C
+110°C
+110°C
+95°C
+95°C
+95°C
+95°C
+95°C
+95°C
+95°C
+95°C
+95°C
AT8060