Omron NJ501-1 Series User Manual page 364

Machine automation controller nj-series cpu unit hardware
Table of Contents

Advertisement

Appendices
Variable name
_CJB_SIO00InitSta
to
_CJB_SIO95InitSta
Meaning
Special I/O Unit Initializing Flags
Function
The corresponding variable is TRUE during initialization of the Special I/O Unit.
The corresponding variable changes to FALSE when the initialization is completed.
The numbers in the variables indicate the unit numbers of the applicable Units.
Data type
BOOL
R/W access
R
Usage in user program
Possible.
Auxiliary
Words
A330 to A335
Area
Bits
A330.00 to A335.15
addresses
Variable name
_CJB_CBU00Restart
to
_CJB_CBU15Restart
Meaning
CPU Bus Unit Restart Bits
Function
The CPU Bus Unit is restarted when the corresponding variable changes to TRUE. (It is changed to FALSE by the
system after the CPU Bus Unit is restarted.)
The numbers in the variables indicate the unit numbers of the applicable Units.
If you change the Restart Flag to TRUE with an instruction, the restart process begins from refresh processing in
the next task period.
Data type
BOOL
R/W access
RW
Usage in user program
Possible.
Auxiliary
Words
A501
Area
Bits
A501.00 to A501.15
addresses
Variable name
_CJB_SIO00Restart
to
_CJB_SIO95Restart
Meaning
Special I/O Unit Restart Bits
Function
The Special I/O Unit is restarted when the corresponding variable changes to TRUE. (It is changed to FALSE by
the system after the CPU Bus Unit is restarted.)
The numbers in the variables indicate the unit numbers of the applicable Units.
If you change the Restart Flag to TRUE with an instruction, the restart process begins from refresh processing in
the next task period.
Data type
BOOL
R/W access
RW
Usage in user program
Possible.
Auxiliary
Words
A502 to A507
Area
Bits
A502.00 to A507.15
addresses
A-122
Retained
Not retained.
Related instruc-
• ResetUnit
tions
Retained
Not retained.
Related instruc-
• ResetUnit
tions
Retained
Not retained.
Related instruc-
• ResetUnit
tions
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
NJ-series CPU Unit Hardware User's Manual (W500)