Variable name
Meaning
Member name
_Card1BkupCmd
SD Memory Card
Backup Com-
(Ver.1.03)
mands
ExecBkup
Execute Backup
Flag
CancelBkup
Cancel Backup
Flag
ExecVefy
Execute Verify
Flag
CancelVefy
Cancel Verify
Flag
DirName
Directory Name
NJ-series CPU Unit Hardware User's Manual (W500)
Function
Change this variable to TRUE to back up Con-
troller data to an SD Memory Card.
Note You cannot use this system-defined
variable in the user program. Use it in
CIP message communications when
sending a command from an HMI or
host computer.
Change this variable to TRUE to cancel back-
ing up data to an SD Memory Card.
Note You cannot use this system-defined
variable in the user program. Use it in
CIP message communications when
sending a command from an HMI or
host computer.
Change this variable to TRUE to compare the
Controller data to a backup file in the SD
Memory Card.
Note You cannot use this system-defined
variable in the user program. Use it in
CIP message communications when
sending a command from an HMI or
host computer.
Change this variable to TRUE to cancel com-
paring the Controller data to a backup file in
the SD Memory Card.
Note You cannot use this system-defined
variable in the user program. Use it in
CIP message communications when
sending a command from an HMI or
host computer.
Used to specify the directory name in the SD
Memory Card for which to back up or verify
data.
Note You cannot use this system-defined
variable in the user program. Use it in
CIP message communications when
sending a command from an HMI or
host computer.
Appendices
Range of
Data type
values
_sBKUP_
CMD
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
BOOL
TRUE or
FALSE
STRING(64) Depends on
data type.
Reference
page A-115
page A-115
page A-115
page A-115
page A-116
page A-116
A-105