 CJ1W-OD232 Transistor Output Unit (32 Points)
Name
Model
Rated Voltage
Operating Load Voltage Range
Maximum Load Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Load Short-circuit Protection
Insulation Resistance
Dielectric Strength
Number of Circuits
Internal Current Consumption
External Power Supply
Weight
Accessories
Circuit Configuration
NJ-series CPU Unit Hardware User's Manual (W500)
32-point Transistor Output Unit with MIL Connector (Sourcing Outputs)
CJ1W-OD232
24 VDC
20.4 to 26.4 VDC
0.5 A/point, 2.0 A/common, 4.0 A/Unit
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance. (Refer to page A-99.)
20 M between the external terminals and the GR terminal (100 VDC)
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of
10 mA max.
32 (16 points/common, 2 circuits)
5 VDC 150 mA max.
20.4 to 26.4 VDC, 70 mA min.
80 g max.
None
SW
Output indicator
ERR indicator
• When an overcurrent is detected, the ERR indicator will light. At the same time, the corresponding
bit (one bit for each common) in the Basic I/O Unit Information Area system-defined variable will
change to TRUE.
Signal name
Allocated
CIO word
COM0 (+V)
COM0 (+V)
Jxx_Ch1_Out00
Wd m
to
Jxx_Ch1_Out15
0 V
COM1 (+V)
COM1 (+V)
Jxx_Ch2_Out00
to
Wd m+1
Jxx_Ch2_Out15
0 V