Using A Cpu Unit With An Earlier Unit Version; Unit Version Settings For Project Devices - Omron NJ501-1 Series User Manual

Machine automation controller nj-series cpu unit hardware
Table of Contents

Advertisement

 Using a CPU Unit with an Earlier Unit Version
If you use a CPU Unit with an earlier version, select the unit version of the connected CPU Unit or an
earlier unit version in the Select Device Area of the Project Properties Dialog Box on the Sysmac
Studio. You can use only the functions that are supported by the unit version of the connected CPU
Unit.
Example:
Precautions for Correct Use
Precautions for Correct Use
An error will occur if you perform the following type of operation.
• Create a project on Sysmac Studio version 1.02 or higher with unit version 1.01 or later
selected as the version in the Select Device Area of the Project Properties Dialog Box.
• Upload the project to Sysmac Studio version 1.01.
Additional Information

Unit Version Settings for Project Devices

• With Sysmac Studio version 1.02 or higher, you can select the unit version in the Select
Device Area of the relevant dialog boxes.
• You can select any unit version that is the same as or earlier than the unit version of the CPU
Unit. For example, if the unit version of the CPU Unit is 1.01, select either 1.00 or 1.01.
• The Sysmac Studio will treat the CPU Unit as a CPU Unit with the unit version that is selected
for the project device. For example, if you set unit version 1.00 for project device, you can use
only the functionality for unit version 1.00 on the Sysmac Studio.
• You can transfer a project to the Sysmac Studio if the unit version that is set for the project
device is the same as or earlier than the unit version of the destination CPU Unit.
• Refer to the Sysmac Studio Version 1 Operation Manual (Cat. No. W504) for details on the
Select Device Area of the relevant dialog boxes.
NJ-series CPU Unit Hardware User's Manual (W500)
Unit version of CPU Unit: 1.03
Sysmac Studio version: 1.05
Unit version 1.04 of the CPU Unit corresponds to Sysmac Studio version 1.05. How-
ever, the connected CPU Unit is unit version 1.03, so select version 1.03 or earlier as
the version in the Select Device Area of the Project Properties Dialog Box. If you select
version 1.03 as the version in the Select Device Area of the Project Properties Dialog
Box, you can use only the functions that are supported by unit version 1.03 of the CPU
Unit. You cannot use functionality that was added for unit version 1.04 or later of the
CPU Unit.
Appendices
A-125