5-2-3

Error Table

The errors (i.e., events) that can occur in the PLC Function Module are given on the following pages.
The following abbreviations and symbols are used in the event level column.
Abbreviation
Maj
Major fault level
Prt
Partial fault level
Min
Minor fault level
Obs
Observation
Info
Information
Symbol
S
Event levels that are defined by the system.
U
Event levels that can be changed by the user.*
* This symbol appears only for events for which the user can change the event level.
A version in parentheses in the Event code column is the unit version of the CPU Unit when the event
was added.
Refer to the NJ-series Troubleshooting Manual (Cat. No. W503) for all NJ-series event codes.

Errors for Self Diagnosis

Event code
Event name
0009 0000 hex
DIP Switch
Setting Error
000D 0000 hex
Internal NJ-
series Bus
Check Error
000E 0000 hex
Non-volatile
Memory Life
Exceeded
1001 0000 hex
Non-volatile
Memory
Restored or
Formatted
1002 0000 hex
Non-volatile
Memory Data
Corrupted
NJ-series CPU Unit Hardware User's Manual (W500)
Name
Meaning
Meaning
Assumed cause
An error was
• There is an error in the DIP
detected in the DIP
switch setting.
switch setting.
A fatal error was
• Conductive material has gotten
detected on the
inside.
internal bus.
• Noise
• The CPU Unit has failed.
The specified num-
• Non-volatile memory life
ber of deletions for
expired.
non-volatile mem-
ory was exceeded.
Or, the number of
bad blocks in mem-
ory exceeded the
specified value.
An error was
• The Controller power supply
detected in the non-
was turned OFF while the
volatile memory
BUSY indicator was lit.
check and file sys-
• The power supply to the Con-
tem recovery or for-
troller was interrupted momen-
matting was
tarily while the BUSY indicator
executed. Previous
was lit.
files may have been
deleted.
A file that must be
• The Controller power supply
in non-volatile
was turned OFF while the
memory is missing
BUSY indicator was lit.
or corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the BUSY indicator
was lit.
• The CPU Unit has failed.
5 Troubleshooting
Level
Maj
Prt
Min
Obs Info
S
page 5-24
S
page 5-24
S
page 5-25
S
page 5-25
S
page 5-26
5
Reference
5-13

Advertisement