5 Troubleshooting
Event name
Unsupported Unit Detected
Meaning
An unsupported CJ-series Unit or Power Supply Unit is mounted.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An unsupported CJ-series Unit or
Power Supply Unit was detected.
Attached
Attached information 1: Rack number where error was detected, 0 to 3
information
Attached information 2: Slot number where error was detected, 0 to 9
Attached information 3: Profile code that gives the Unit type
Precautions/
This error will not occur for unsupported Power Supply Units that are mounted on Expansion Rack. Make sure that the
Remarks
Power Supply Units connected to the Expansion Racks are supported before using them.
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
Event name
Too Many I/O Points
Meaning
The total number of I/O points in the connected CJ-series Units exceeds the maximum specified value of the CPU Unit.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The total number of I/O points in the
connected CJ-series Basic I/O Units
exceeds 2,560.
Attached
Attached information 1: Total number of I/O points in the CJ-series Basic I/O Units
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
5-36
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Remove the unsupported CJ-series
CPU Unit or Power Supply Unit and
replace it with a supported one.
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Set the total number of I/O points in
the CJ-series Basic I/O Units to 2,560
or less.
Event code
2401 0000 hex
I/O bus master
Detection
timing
Cycle the power
Log category
supply.
Stops.*
Name
---
Prevention
Use a Unit that is supported by this
CPU Unit.
Event code
2402 0000 hex
I/O bus master
Detection
timing
Cycle the power
Log category
supply.
Stops.*
Name
---
Prevention
Set the total number of I/O points in
the CJ-series Basic I/O Units to 2,560
or less.
NJ-series CPU Unit Hardware User's Manual (W500)
At power ON or
Controller reset
System
At power ON or
Controller reset
System