Omron NJ501-1 Series User Manual page 183

Machine automation controller nj-series cpu unit hardware
Table of Contents

Advertisement

Event code
Event name
102D 0000 hex
CJ-series
(Ver. 1.03)
Unit Backup
Failed
102E 0000 hex
CJ-series
(Ver. 1.03)
Unit Restore
Operation
Failed
3020 0000 hex
Unsupported
(Ver. 1.02)
Unit Setting
8001 0000 hex
Illegal Packet
Discarded
NJ-series CPU Unit Hardware User's Manual (W500)
Meaning
Assumed cause
The backup opera-
• An error occurred in the Unit
tion for a CJ-series
Configuration.
Unit ended in an
• An error occurred for a Special
error.
Unit.
• A restart is in progress for the
Special Unit.
• A Unit model or Special Unit
unit number in the Unit Configu-
ration in the CPU Unit is differ-
ent from the Unit model or the
Special Unit unit number of the
Unit that is mounted in the Con-
troller.
• The CPU Unit or CJ-series Unit
has failed.
The restore opera-
• An error occurred in the Unit
tion for a CJ-series
Configuration.
Unit ended in an
• An error occurred for a Special
error.
Unit.
• The Unit Configuration in the
backup file does not agree with
the physical Unit configuration.
• A restart is in progress for the
Special Unit.
• The restore conditions that are
required by the Special Unit are
not met.
• The backup files are corrupted.
• The CPU Unit or CJ-series Unit
has failed.
A setting in the
• A setting in the Special Unit is
Special Unit is not
not supported by the CPU Unit.
supported.
An illegal packet
• Noise
was received during
message communi-
cations. The illegal
packet was dis-
carded.
5 Troubleshooting
Level
Maj
Prt
Min
Obs Info
S
page 5-41
S
page 5-42
S
page 5-43
S
page 5-43
Reference
5
5-17

Advertisement

Table of Contents
loading