8.2.2 Connectors

Fieldbus interface
Fig. 25 Male Connector DeviceNet
No:
1
2
3
4
5
Note
The layout in Fig. 25 Male Connector DeviceNet is for a male connector. Female connectors
are in the opposite order.
8.3

DeviceNet network setup

To be able to setup the DeviceNet fieldbus network, the AnyBus NetTool for DeviceNet is
recommended to use.
Reg.No. ME00107EN-02
Indication
Operation mode
Network status
Module status
1
2
Signal
Decription
V-
Negative supply voltage
CAN_L
CAN_L bus line
shield
Cable shield
CAN_H
CAN_H bus line
V+
Positive supply voltage
Meaning
State
-
No power or not initialized
Green, flashing
Idle mode
Green
Run mode
Off
No power, not initialized or no
connection established
Green, flashing
Online, no connection established
Green
Online, at least one connection
established
Red, flashing
Minor fault; at least one connection
has a minor fault
Red
Critical link failure
Off
No power or not initialized
Green
Module status OK
Red, flashing
Minor fault
Red
Major fault
3
4
5
Fieldbus PCI-Card
DeviceNet network setup
Note
The module requires 24VDC bus
power
The module requires 24VDC bus
power
Page 37