Fieldbus PCI-Card

DeviceNet network setup

No:
5
6

7.2.2 Connectors

Application interface
The module is available in both serial and parallel versions.
Fieldbus interface
Fig. 23 Male Connector DeviceNet
No:
1
2
3
4
5
Note
The layout in Fig. 23 Male Connector DeviceNet is for a male connector. Female connectors
are in the opposite order.
7.3
DeviceNet network setup
For a complete network setup See 8.3 DeviceNet network setup. Each slave device in a DeviceNet
network is associated with an EDS-file which has to be downloaded to the network.
Page 34
Indication
Network status
Module status
1
2
Signal
Decription
V-
Negative supply voltage
CAN_L
CAN_L bus line
shield
Cable shield
CAN_H
CAN_H bus line
V+
Positive supply voltage
Meaning
State
Off
No power or not online
Green
Link OK, online, connected
Green, flashing
Online not connected
Red
Critical link failure
Red, flashing
Connection timeout
Off
No power to device
Green
Device operational
Green, flashing
Data size greater than configured
Red
Unrecoverable fault
Red, flashing
Minor fault
3
4
5
Note
The module requires 24VDC bus
power
The module requires 24VDC bus
power