Monitor Parameters
This section explains the analog monitor and pulse monitor parameters.
K K K K
Using the Analog Monitor Parameters
This section explains the analog monitor parameters.
nRelated Parameters
Param-
eter
Num-
ber
Monitor selection (termi-
nal FM)
H4-01
Terminal FM Sel
Gain (terminal FM)
H4-02
Terminal FM Gain
Bias (terminal FM)
H4-03
Terminal FM Bias
Monitor selection (termi-
nal AM)
H4-04
Terminal AM Sel
Gain (terminal AM)
H4-05
Terminal AM Gain
Bias (terminal AM)
H4-06
Terminal AM Bias
Analog output 1 signal
level selection
H4-07
AO Level Select1
Analog output 2 signal
level selection
H4-08
AO Level Select2
-72
6
Name
LCD Display
Sets the number of the monitor item to be output
(U1-oo) from terminal FM.
4, 10 to 14, 28, 34, 39, 40 cannot be set. 17, 23, 25,
29, 30, 31, 35 are not used.
Sets the multi-function analog output 1 voltage
level gain.
Sets whether the monitor item output will be out-
put in multiples of 10 V.
The maximum output from the terminal is 10 V.
Sets the multi-function analog output 1 voltage
level bias.
Sets output characteristic up/down parallel move-
ment as a percentage of 10 V.
The maximum output from the terminal is 10 V.
Sets the number of the monitor item to be output
(U1-oo) from terminal AM.
4, 10 to 14, 28, 34, 39, 40 cannot be set. 17, 23, 25,
29, 30, 31, 35 are not used.
Set the voltage level gain for multi-function ana-
log output 2.
Set the number of multiples of 10 V to be output
as the 100% output for the monitor items. The
maimum output from the terminal is 10 V.
Set the multi-function analog output 2 voltage
level bias.
Sets output characteristic up/down parallel move-
ment as a percentage of 10 V.
The maximum output from the terminal is 10 V.
Sets the signal output level for multi-function
output 1 (terminal FM)
0: 0 to 10 V output
1: 0 to ±10 V output
(2: 4 to 20 mA)*
Sets the signal output level for multi-function out-
put 2 (terminal AM)
0: 0 to +10 V output
1: 0 to ±10 V output
(2: 4 to 20 mA)*1
Setting
Description
Range
1 to 40
0.00 to
2.50
(0.0 to
1000.0)
-10.0 to
+10.0
(-100.0 to
+110.0)
1 to 40
0.00 to
2.50
(0.0 to
1000.0)
-10.0 to
+10.0
(-100.0 to
+110.0)
0 or 1
(0 to 2)
0 or 1
(0 to 2)
Control Methods
Change
Factory
during
Setting
Opera-
V/f
tion
2
No
A
1.00
Yes
Q
(100.0%)
*1
*1
0.0%
Yes
A
*1
3
No
A
0.50
Yes
Q
(50.0%)
*1
*1
0.0%
Yes
A
*1
0
No
A
*1
0
No
A
*1
Open
V/f
Loop
with
Vec-
PG
tor
A
A
Q
Q
A
A
A
A
Q
Q
A
A
A
A
A
A