Setting Motor Constant Parameters

In vector control method, the motor constant parameter are set automatically using autotuning. If autotuning
does not complete normally, set them manually.
nRelated Parameters
Name
Param-
eter
Num-
LCD Display
ber
Motor rated current
E2-01
Motor Rated FLA
Motor rated slip
E2-02
Motor Rated Slip
Motor no-load current
E2-03
No-Load Current
Number of motor poles
E2-04
Number of Poles
Motor line-to-line resis-
tance
E2-05
Term Resistance
Motor leak inductance
E2-06
Leak Inductance
Motor iron saturation coef-
ficient 1
E2-07
Saturation Comp1
Motor iron saturation coef-
ficient 2
E2-08
Saturation Comp2
Motor iron loss for torque
compensation
E2-10
Tcomp Iron Loss
Note All factory-set parameters are for a standard 4-pole motor.
* 1. The factory settings depend on Inverter capacity (the values shown are for a 200 V Class Inverter for 0.4 kW).
* 2. The setting range is 10% to 200% of the Inverter rated output current (the values shown are for a 200 V Class Inverter for 0.4 kW).
* 3. The setting range depends on Inverter capacity (the values shown are for a 200 V Class Inverter for 0.4 kW).
Description
Sets the motor rated current in 1 A units.
These set values will become the reference values
for motor protection and torque limits.
This parameter is automatically set during auto-
tuning.
Sets the motor rated slip in Hz units.
These set values will become the reference values
for slip compensation.
This parameter is automatically set during auto-
tuning.
Sets the motor no-load current in 1 A units.
This parameter is automatically set during auto-
tuning.
Sets the number of motor poles.
This parameter is automatically set during auto-
tuning.
Sets the motor phase-to-phase resistance in Ω
units.
This parameter is automatically set during auto-
tuning.
Sets the voltage drop due to motor leakage induc-
tance as a percentage of the motor rated voltage.
This parameter is automatically set during auto-
tuning.
Sets the motor iron saturation coefficient at 50%
of magnetic flux.
This parameter is automatically set during auto-
tuning.
Sets the motor iron saturation coefficient at 75%
of magnetic flux.
This parameter is automatically set during auto-
tuning.
Sets motor iron loss in W units.
Individual Functions
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0.32 to
1.90 A
6.40
No
Q
*1
*2
0.00 to
2.90 Hz
No
A
20.00
*1
0.00 to
1.20 A
1.89
No
A
*1
*3
2 to 48
4 poles
No
No
0.000
9.842 Ω
to
No
A
*1
65.000
0.0 to
18.2%
No
No
40.0
0.00 to
0.50
No
No
0.50
0.00 to
0.75
No
No
0.75
0 to
14 W
No
A
65535
*1
Open
V/f
Loop
with
Vec-
PG
tor
Q
Q
A
A
A
A
Q
No
A
A
No
A
No
A
No
A
A
No