Factory Settings That Change With The Control Method (A1-02) - Omron SYSDRIVE 3G3RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

K K K K

Factory Settings that Change with the Control Method (A1-02)

The factory settings of the following parameters will change if the control method (A1-02) is changed.
Param-
eter
Number
b3-01 Speed search selection
b3-02 Speed search operating current
C3-01 Slip compensation gain
Slip compensation primary delay time
C3-02
constant
Torque compensation primary delay time
C4-02
constant
E1-04
Max. output frequency (FMAX)
E3-02
E1-05
Max. voltage (VMAX)
E3-03
E1-06
Base frequency (FA)
E3-04
E1-07
Mid. output frequency (FB)
E3-05
E1-08
E3-06 Mid. output frequency voltage (VC)
E1-09
Min. output frequency (FMIN)
E3-07
E1-10
E3-08 Min. output frequency voltage (VMIN)
* 1. The settings shown are for 200-V class Inverters. The values will double for 400-V class Inverters.
* 2. Settings vary as shown in the following tables depending on the Inverter capacity and E1-03.
Name
Setting Range
0 to 10000
0 to 10000
0.0 to 400.0
0.0 to 255.0
0.0 to 400.0
0.0 to 400.0
0.0 to 255.0
*1
(0.0 to 510.0)
0.0 to 400.0
0.0 to 255.0
*1
(0.0 to 510.0)
V/f Con-
Unit
A1-02=0
0 to 3
1
0 to 200
1%
0.0 to 2.5
0.1
1 ms
2000
1 ms
0.1 Hz
200.0
0.1 V
0.1 Hz
0.1 Hz
0.1 V
0.1 Hz
0.1 V
Parameter Tables
Factory Setting
Open
V/F with
Loop
trol
PG
Vector
A1-02=1
A1-02=2
2
3
2
120
-
100
0.0
-
1.0
-
200
200
200
20
60.0
60.0
60.0
*2
*2
200.0
200.0
*2
*2
60.0
60.0
60.0
*2
*2
3.0
3.0
3.0
*2
*2
15.0
15.0
11.0
*2
*2
1.5
1.5
0.5
*2
*2
9.0
9.0
2.0
*2
*2
83