Monitor
2-5-2
Calibration of Frequency Meter
Description
Select PRGM Mode.
Select constant (No. 45).
Data are displayed.
Change the set value.
2-6
Monitor
Typical Monitor Contents and Display
Calibration of frequency meter or ammeter connected to the
Inverter can be performed even without providing a calibration
resistor.
Example
When the frequency meter specifications are 3 V and 1 mA scale,
operation is performed at 60 Hz with a frequency setting voltage of
10 V.
Key Operation
PRGM
ENTER
NO
DSPL
DATA
ENTER
RESET
DATA
ENTER
No. 45
FREQ. meter calibration
Frequency reference value, output frequency, output current and
fault contents can be monitored.
The monitor item is changed every time when the NO/DSPL Key is
pressed.
Digital Operator Display
+
–
12
FM
3 V, 1 mA
11
Section 2-6
. . . 10 V 0.3 = 3.0 V