Protective And Diagnostic Functions; Fault Detection - Omron SYSDRIVE 3G3RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

Protective and Diagnostic Functions

This section describes the alarm functions of the Inverter. The alarm functions include fault detection,
alarm detection, operation error detection, and autotuning error detection.
K K K K

Fault Detection

When the Inverter detects a fault, the fault contact output operates, and the Inverter output is shut OFF causing
the motor to coast to a stop. (The stopping method can be selected for some faults, and the selected stopping
method will be used with these faults.) A fault code is displayed on the Digital Operator.
When a fault has occurred, refer to the following table to identify and correct the cause of the fault.
Use one of the following methods to reset the fault after restarting the Inverter:
Set a multi-function contact input (H1-01 to H1-05) to 14 (Fault Reset) and turn ON the error reset signal.
Press the RESET Key on the Digital Operator.
Turn the main circuit power supply OFF and then ON again.
Display
Overcurrent
The Inverter output current exceeded
Over
the overcurrent detection level. (200%
Current
of rated current)
Ground Fault
The ground fault current at the
Inverter output exceeded approxi-
Ground
mately 50% of the Inverter rated out-
Fault
put current.
Fuse Blown
DC BUS
The fuse in the main circuit is blown.
Fuse Open
Main Circuit Overvoltage
The main circuit DC voltage exceeded
the overvoltage detection level.
DC Bus
200 V class: Approx. 410 V
Overvolt
400 V class: Approx. 820 V
-2
7
Table 7.1 Fault Displays and Processing
Meaning
• A short-circuit or ground fault
occurred at the Inverter output. (A
short or ground fault can be caused
by motor burn damage, worn insu-
lation, or a damaged cable.)
• The load is too large or the accelera-
tion/deceleration time is too short.
• A special-purpose motor or motor
with a capacity too large for the
Inverter is being used.
• A magnetic switch was switched at
the Inverter output.
A ground fault occurred at the Inverter
output. (A ground fault can be caused
by motor burn damage, worn insula-
tion, or a damaged cable.)
The output transistor has failed
because of a short-circuit or ground
fault at the Inverter output.
Check whether there is a short-circuit
between the following terminals. A
short-circuit will damage the output
transistor:
B1 (
The deceleration time is too short and
the regenerative energy from the
motor is too large.
The power supply voltage is too high.
Probable Causes
3)
U, V, W
U, V, W
Corrective Actions
Reset the fault after correcting its
cause.
Reset the fault after correcting its
cause.
Replace the Inverter after correct-
ing the cause.
Increase the deceleration time or
connect a braking resistor (or
Braking Resistor Unit).
Decrease the voltage so it's within
specifications.

Advertisement

Table of Contents

Troubleshooting