Undertorque Detection
L6-02 or L6-05
Undertorque detection 1 NO
or Undertorque detection 2 NO
K K K K
Changing Overtorque and Undertorque Detection Levels Using an Ana-
log Input
If you set parameter H3-09 (Multi-function Analog Input Terminal A2 Function Selection) to 7 (overtorque/
undertorque detection level), you can change the overtorque/undertorque detection level.
If you change the overtorque/undertorque detection level using the multi-function analog input, only over-
torque/undertorque detection level 1 will be enabled.
The following diagram shows the overtorque/undertorque detection level using an analog input.
Multi-Function Analog Input (H3-09)
Set
Value
7
Overtorque/Undertorque Detection Level
-46
6
Motor current (output torque)
L6-03
or
L6-06
The undertorque detection disabled margin is approximately 10% of the Inverter rated output
current (or motor rated torque)
Detection level
(4 mA)
Fig 6.38 Overtorque/Undertorque Detection Level Using an Analog Input
Function
*
L6-03
or
L6-06
ON
Multi-function analog input
terminal A2 input level
(20 mA)
Content at 100%
Motor rated torque (vector control), Inverter rated current (V/f con-
trol)
ON
Control Methods
V/f
V/f
with
PG
Yes
Yes
Open
loop
Vec-
tor
Yes