U: Monitor Parameters - Omron I537-E2-01 User Manual

Table of Contents

Advertisement

Name
Param-
eter
LCD
Number
Display
Motor rated
current
Set the rated current of the motor
T1-04
in Amps.
Rated Current

U: Monitor Parameters

The following settings are made with the monitor parameters (U parameters): Setting parameters for monitor-
ing in drive mode.
Status Monitor Parameters: U1
Name
Param-
eter-
LCD
Number
Display
Frequency
reference
Monitors/sets the frequency ref-
U1-01
Frequency
erence value.*
Ref
Output fre-
quency
U1-02
Monitors the output frequency.*
Output Freq
Output current
U1-03
Monitors the output current.
Output Cur-
rent
Output volt-
Monitors the output voltage refer-
age
U1-06
Output Volt-
ence value in the Inverter.
age
DC bus volt-
Monitors the main DC voltage in
age
U1-07
DC Bus Volt-
the Inverter.
age
Output power
Monitors the output power (inter-
U1-08
Output kWatts
nal detected value)
Input terminal
Shows input ON/OFF status.
status
U1-10
Input Term Sts
Setting
Description
Range
0.32 to
6.40
Output Signal Level During Multi-
Description
Function Analog Output
10 V: Max. frequency
(0 to + 10 V possible)
10 V: Max. frequency
(0 to + 10 V possible)
10 V: Inverter rated output
current
(0 to +10 V, absolute value
output)
10 V: 200 VAC (400 VAC)
(0 to +10 V output)
10 V: 400 VDC (800 VDC)
10V: Inverter maximum
capacity (max. appli-
cable motor capacity)
(0 to +10 V possible)
1: FWD command
(S1) is ON
1: REV command
(S2) is ON
1: Multi input 1
(S3) is ON
1: Multi input 2
(Cannot be output.)
(S4) is ON
1: Multi input 3
(S5) is ON
1: Multi input 4
(S6) is ON
1: Multi input 5
(S7) is ON
Change
RS-422A/
Factory
during
Access
485
Setting
Opera-
Level
Register
tion
1.90 A
No
A
704H
Min.
Access
Unit
Level
0.00
A
Hz
0.00
A
Hz
0.0
A
A
0.0
A
V
0 V
A
0.0
kW
-
A
Parameter Tables
Page
4-8
RS-422A/
485
Register
40H
41H
42H
45H
46H
49H
37