Table 2.9 Closed-loop Connector Sizes (JIS C2805) (200-V class and 400-V class)
Wire Thickness (mm
IMPORTANT
-18
2
2
)
0.5
0.75
1.25
2
3.5/5.5
8
14
22
30/38
50/60
80
100
100
150
200
325
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
Line voltage drop (V) =
3
x wire resistance (W/km) x wire length (m) x current (A) x 10
Terminal Screws
M3.5
M4
M3.5
M4
M3.5
M4
M3.5
M4
M5
M6
M8
M4
M5
M6
M8
M5
M6
M8
M6
M8
M6
M8
M8
M8
M10
M10
M12
M12 x 2
M16
Size
1.25 to 3.5
1.25 to 4
1.25 to 3.5
1.25 to 4
1.25 to 3.5
1.25 to 4
2 to 3.5
2 to 4
2 to 5
2 to 6
2 to 8
5.5 to 4
5.5 to 5
5.5 to 6
5.5 to 8
8 to 5
8 to 6
8 to 8
14 to 6
14 to 8
22 to 6
22 to 8
38 to 8
60 to 8
60 to 10
80 to 10
100 to 10
100 to 12
150 to 12
200 to 12
325 to 12
325 to 16