6.3 DATA TO CONTACT THE TECHNICAL ASSISTANCE

For information or service request, it is important to have at hand the following data:
Drive model.
Serial number and manufacturing date of the product found in the identification label
(refer to
section 2.4 - Identification
Software version installed (see P0023 and P0024).
Information about the application and programming executed.

6.4 PREVENTIVE MAINTENANCE

DANGER!
Always disconnect the general power supply before changing any electric
component associated to the drive.
High voltages can be present even after the disconnection of the power
supply. Wait for at least ten minutes for the full discharge of the power
capacitors. Always connect the frame of the equipment to the protection
grounding (PE) at the proper point for that.
ATTENTION!
The electronic boards have components sensitive to electrostatic
discharges.
Do not touch components or connectors directly. If necessary, first touch
the grounded metallic frame or use a proper grounding strap.
Do not execute any applied potential test on the drive. If necessary,
contact WEG.
When installed in proper environment and operating conditions, the drives require little
service.
Table 6.2
lists the main procedures and intervals for routine maintenance.
6.3
suggests inspections on the product every 6 months after start-up.
Maintenance
Internal fan replacement
If the drive
is stocked (not
in use):
Electrolytic
"Reforming"
capacitors
Drive being
used: replace
Labels).
Table 6.2: Preventive maintenance
Interval
After 40,000 hours of operation.
Every year from the
manufacturing date printed on
the drive identification label
(refer to
section 2.5 - Receiving
and
Storage).
Every 10 years.
- English -
Troubleshooting and Maintenance
Instructions
Replacement.
Apply power to the drive with
voltage between 380 and 480 Vac,
single-phase or three-phase, 50 or
60 Hz, for at least one hour. Then,
disconnect the power supply
and wait for at least 24 hours before
using the drive (reapply power).
Contact WEG technical support to
obtain replacement procedure.
Table
MW500 | 33