Installation and Connection

3.2.4 Grounding Connections

DANGER!
The drive must be connected to a protection grounding (PE).
Use grounding wiring with a gauge at least equal to that indicated in
table
The maximum tightening torque of the grounding connections is of
1.7 N.m (15 lbf.in).
Connect the grounding points of the drive to a specific grounding
rod, or specific grounding point or to the general grounding point
(resistance ≤ 10 Ω).
Do not share the grounding wiring with other equipment that operate
with high currents (e.g. high power motors, soldering machines, etc.).

3.2.5 Control Board

Plug-in modules are connected to control board. S10 DIP-switch are available in control
board, for more information refer to

3.2.6 Control Connections

The control connections (analog input/output, digital input/output and interface RS485)
must be performed according to the specification of the connector of the plug-in module
connected to the MW500. Refer to the guide of the plug-in module in print or in the CD
of the product. The typical functions and connections for the CFW500-IOS standard
plug-in module are shown in
the connector signals, refer to
14 | MW500
Figure 3.3: Details of the connection of the motor cable
B.1.
section 4.3 - Operating Modes of the
figure
3.4. For further details about the specifications of
chapter 8 - Technical
Specifications.