Troubleshooting and Maintenance

5 TROUBLESHOOTING AND MAINTENANCE

5.1 FAULTS AND ALARMS

NOTE!
Refer to the ADW300 quick reference and the programming manual for further
information on each fault or alarm.

5.2 SOLUTION FOR THE MOST FREQUENT PROBLEMS

Problem
Point to be Verified
Motor will not
Incorrect wiring
start
Incorrect settings
Fault
Motor stall
Motor speed
Loose connections
oscillates
Oscillation of the
external analog
reference
Too high or
Incorrect settings
too low motor
(reference limits)
speed
Motor nameplate
Led is off
Power supply voltage
Mains supply fuses
open

5.3 INFORMATION NECESSARY FOR CONTACTING TECHNICAL SUPPORT

For technical support or servicing, it is important to have the following information in hand:
Inverter model.
Serial number and manufacturing date listed in the product nameplate (refer to
IDENTIFICATION LABEL on page
Installed Software version (refer to P023).
Data on the application and inverter settings.
20 | ADW300
Table 5.1: Solution for the most frequent problems
1. Check all power and control connections
1. Check if the parameter values are correct for the
application
1. Check whether the inverter is disabled due to a fault
condition
1. Decrease the motor overload
2. Increase P136, P137 (V/f)
1. Stop the inverter, turn off the power supply, check and
tighten all the power connections
2. Check all the internal connections of the inverter
1. Identify the cause of the oscillation. If the cause is electrical
noise, use shielded cables or separate them from the
power or command wiring
2. Interconnect the GND of the analog reference to the
grounding connection of the inverter
1. Check whether the values of P133 (minimum speed) and
P134 (maximum speed) are properly set for the used
motor and application
1. Check whether the used motor matches the application
1. Rated values must be within the limits specified below:
200 / 240 V power supply: Min: 170 V - Max: 264 V
110 / 127 V power supply: Min: 93 V - Max: 140 V
1. Replace the fuses
5).
Corrective Action
Section 2.4