Installation And Connection - WEG MW500 User Manual

Frequency inverter
Hide thumbs Also See for MW500:
Table of Contents

Advertisement

Digital input 2 (DI2) can also be used as input in frequency (FI). For further details refer to the programming manual of the
(*)
MW500.
For further information, refer to the detailed specification in
(**)
Figure 3.4: Signals of the connector of the CFW500-IOS plug-in module
The location of the plug-in module and DIP-switches to select the type of analog input
and output signal and the termination of the RS485 network is shown in
The MW500 drives are supplied with the digital inputs configured as active low (NPN),
analog input and output configured for signal in voltage 0...10 V and with the termination
resistor of the RS485 OFF.
NOTE!
To use the analog inputs and/or outputs with signal in current, you
must set switch S1 and related parameters as per
information, refer to the MW500 programming manual.
To modify the digital inputs from active low to active high, check the
use of parameter P0271 in the MW500 programming manual.
Connector
1
3
5
7
9
11 DO1-RL-NA
13
DO1-RL-C
15 DO1-RL-NF
2
4
6
8
10
DO2-TR
12
RS485 - A
14
RS485 - B
16
section 8.2 - Electronics/General
- English -

Installation and Connection

Description
DI1
Digital Input 1
DI2
Digital Input 2
DI3
Digital Input 3
DI4
Digital Input 4
+24 V
Power Supply +24 Vdc
Digital Output 1
(Relay NO Contact 1)
Digital Output 1
(Relay Common Point 1)
Digital Output 1
(Relay NC Contact 1)
AO1
Analog Output 1
GND
Reference 0 V
AI1
Analog Input 1
Reference +10 Vdc for
+10 V
Potentiometer
Digital Output 2 (Transistor)
RS485 (Terminal A)
RS485 (Terminal B)
GND
Reference 0 V
Data.
figure
table
3.1. For further
MW500 | 15
(**)
(*)
A.1.