Powering up and Start-up
Seq
Indication on the Display / Action
11
If necessary, modify the content of "P0403 –
Motor Rated Frequency", or press the Key 
for the next parameter.
12
If necessary, modify the content of "P0404 –
Motor Rated Power", or press the key  for
the next parameter.
13
If necessary, modify the content of "P0407 –
Motor Rated Power Factor", or press the key
 for the next parameter.
14
At this point, the HMIR shows the option to do
the self-adjustment. Whenever possible, perform
the self-adjustment. Thus, to activate the self-
adjustment, change the value of P0408 to "1".
15
During the Self-Adjustment the HMIR will
simultaneously indicate the status of "RUN"
and "CONF". And the bar graph indicates the
progress of the operation.
And the bar graph indicates the progress of
the operation. The Self-Adjustment can be
interrupted at any time by means of the key
Figure 5.5 (cont.): Sequence of the Start-up group for V V W control
30 | MW500
Seq
Indication on the Display / Action
16
At the end of the Self-Adjustment, the value
of P0408 automatically returns to "0", as
well as the Status of "RUN" and "CONF"
are cleared.
Press the key  for the next parameter.
17
The result of Self-Adjustment is the value
in ohms of the motor stator resistance
shown in P0409.
This is the last parameter of the Self-
Adjustment of the V V W control mode.
Press the key  to return to initial
parameter P0202.
18
To exit the STARTUP menu, just press
BACK/ESC.
19
Through the keys  and , select the
desired menu or press the key BACK/ESC
again to return directly to the monitoring
mode of the HMIR.
.