Grounding Connections - WEG CFW701 User Manual

Table of Contents

Advertisement

Installation and Connection
Figure 3.4: Motor cable shielding connection with PCSx-01 accessory

3.2.4 Grounding Connections

DANGER!
The inverter shall be connected to a Protective Ground (PE).
Use the minimum ground wiring gauge as indicated in the
151,
Table B.2 on page 152
Connect the inverter grounding connections to a ground bus bar, to a single
ground point, or to a common grounding point (impedance ≤ 10 Ω).
The neutral conductor of the network shall be solidly grounded; however,
this conductor shall not be used to ground the inverter.
It is necessary to use a copper cable with 10 mm
the same wire gauge as specified in
page 152
ground protection to be in accordance with IEC61800-5-1 since the leakage
current is greater than 3.5 mA AC.
DANGER!
Le variateur doit être raccordé à une terre de protection (PE).
Utilisez la section minimale de raccordement à la terre indiquée dans les
B.1 à la page
Connectez la masse du variateur à une barre c llectrice de terre en un seul
point ou à un point commun de raccordement à la terre (impédance ≤ 10 Ω).
Le conducteur neutre doit être solidement raccordé à la terre; néanmoins,
ce conducteur ne doit pas s'utiliser pour raccorder le variateur à la terre.
Il est nécessaire d'utiliser un câble de section minimale 10 mm
de section identique (voir les
152
et
conformément à la norme IEC61800-5-1 du fait que le courant de fuite
alternatif est supérieur à 3.5 mA.
18 | CFW701
and
and
Table B.3 on page 153
151,
Table B.2 à la page 152
Table B.1 à la page
Table B.3 on page 153
Table B.3 on page
153.
minimum or 2 cables with
²
Table B.1 on page
for connecting the inverter to the
et
Table B.3 on page
151,
pour raccorder le variateur à la terre
Table B.1 on page
151,
Table B.2 on
Table
153.
ou 2 câbles
²
Table B.2 on page