3.2.4 Grounding Connections

DANGER!
The inverter must be connected to a protective ground (PE).
Use a minimum wire gauge for ground connection equal to the indicated in
Table B1 on page
Connect the inverter grounding connections to a ground bus bar, to a single
ground point or to a common grounding point (impedance ≤ 10 Ω).
The neuter conductor of the line that feeds the inverter must be solidly
grounded; however, this conductor must not be used to ground the inverter.
Do not share the grounding wiring with other equipment that operate with high
currents (e.g.: high voltage motors, welding machines, etc.).

3.2.5 Control Connections

The control connections must be made in accordance with the specification of the connector
of the CFW300 control board. Functions and typical connections are presented in
page
17. For further details on the specifications of the connector signals, refer to
8 TECHNICAL SPECIFICATIONS on page
1
2
3
4
5
6
(+) AI1 (-)
(0 a 20) mA
(4 a 20) mA
(a) NPN Configuration
1
2
3
4
5
6
24 V
(+) AI1 (-)
(0 a 20) mA
(External supply)
(4 a 20) mA
(b) PNP Configuration
NOTE!
The CFW300 inverters are supplied with the digital inputs configures as active
low (NPN). In order to change the configuration, check the use of parameter
P271 in the programming manual of the CFW300.
Analog input AI1 is set for input 0 to 10 V, in order to change, check parameter
P233 of the programming manual.
113.
31.
7
8
9
10
11
12
AI1
(0 a 10) V
7
8
9
10
11
12
AI1
(0 a 10) V
Figure 3.3: (a) and (b) Signals of C300 control card connector
Installation and Connection
Connector
1
DI1
Digital input 1
2
DI2
Digital input 2
3
DI3
Digital input 3
4
DI4
Digital input 4
5
GND
Reference 0 V
6
AI1
Analog input 1
(Current)
7
GND
Reference 0 V
8
AI1
Analog input 1
(Tension)
9
+10 V
Reference +10 Vdc
for potentiometer
10
DO1-RL-NC
Digital output 1
(NC contact of relay 1)
11
DO1-RL-C
Digital output 1
(Common point of relay 1)
12
DO1-RL-NO
Digital output 1
(NO contact of relay 1)
(*) For further information, refer to the detailed specification in
Section 8.2 ELECTRONICS/GENERAL DATA on page
Figure 3.3 on
Chapter
Description
(*)
32.
CFW300 | 17