System Does Not Start-up
Thermostat Light is Off
Possible Cause
Voltage switch not in correct position
No power to outlet
Unit not plugged in
LCDI tripped
Thermostat Light is On
Possible Cause
Thermostat is not set up properly
System is Operating and Blows Evaporator Air, but the
Supply Air is Not Colder Than the Return Air from the Cellar
Possible Cause
Thermostat not set up properly
Compressor not operating
Condenser airflow is blocked
Head Pressure (HP) switch is open
32
Solution
Check position
Check circuit breaker and wiring
Plug in the system
Reset
Solution
Check thermostat set up in the guide.
Solution
Check thermostat setup in the manufacture's
thermostat guide
High pressure switch open (button up) (see
below)
Remove blockage
Clean coil (if needed)
Reset HP switch See reset instructions on
page 27