RUN THE GAS LINE.
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with local building codes.
GAS CONVERSIONS
If a gas conversion is necessary, one of the following conversions kits must be used:
Natural Gas Conversion Kit #OCK-H50N - used to convert an LP Gas millivolt board to natural gas.
LP Gas Conversion Kit #OCK-H57L - used to convert a Natural Gas millivolt board to LP Gas.
The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and in
accordance with the requirements of the ANSI Z223.1 installation code.
NOTE: This fireplace is equipped with a 3/8" x 12" long flexible gas connector and manual shut off valve.
NOTE: The gas line should be run to the point of connection where the shut-off valve and flexible gas line will connect.
CAUTION:
The manual shut-off valve or flexible gas tubing must not extend outside of the fireplace cavity. See the WARNING label
affixed to the flexible tubing for additional installation instructions and warnings.
NATURAL GAS:
The minimum inlet gas supply pressure: 5.0 inches W.C. ( 7.0 inches W.C. recommended)
The maximum inlet gas supply pressure: 10.5 inches W.C.
Manifold pressure: 3.5 inches W.C.
Manifold pressure (lo setting): 1.7 inches W.C.
Orifices sizes: #50 Input: 14,600 BTU/hr.
LP GAS:
The minimum inlet gas supply pressure: 11.0 inches W.C. (recommended)
The maximum inlet gas supply pressure: 13.0 inches W.C.
Manifold Pressure: 10.0 inches W.C.
Manifold Pressure (lo setting): 6.5 inches W.C.
Orifices size: #57
This fireplace is equipped for use at altitudes of 0-2,000 ft. in the U.S. and 0-4,500 ft. in Canada.
NOTE:
For high altitude installations consult the local gas distributor or the authority having jurisdiction for proper rating methods.
1.
Run the gas line. Gas line holes are positioned on both sides of the fireplace for gas line connection. An accessible shut off valve
(included) must be installed up stream from the regulator.
NOTE: Do not run the incoming gas line in a manner that would obstruct the operation of the optional fan.
2 . This fireplace is designed to accept either a 3/8" or 1/2" gas line approved for gas appliances. Consult local building codes to
properly size the gas supply line leading to a 3/8" reduction.
Minimum input: 10,700 BTU/hr.
Input: 14,700 BTU/hr.
Minimum input:
10,700 BTU/hr.
Page 14