Installation; Location Of Ice Machine - Manitowoc S300 Technician's Handbook

S series
Table of Contents

Advertisement

PERSONAL INJURY POTENTIAL
Remove a ll i ce machi ne p anels before lifting a nd
installing.

Location of Ice Machine

The location selected for the ice machine head section
must meet the following criteria. If any of these criteria
are not met, select another location.
The location must be free of airborne and other
contaminants.
Self contained air and water cooled - The air
temperature must be at least 35°F (1.6°C), but
must not exceed 110°F (43.4°C).
Remote air cooled - The air temperature must be
at least -20°F (-29°C), but must not exceed 120°F
(49°C)
Ice Making Water Inlet - Water Pressure must be
at least 20 psi (1.38 bar), but must not exceed 80
psi (5.52 bar).
Condenser Water Inlet - Water Pressure must be
at least 20 psi (1.38 bar), but must not exceed
150 psi (10.34 bar). S3300W-HP units allow water
pressure up to 350 psig (24.13 bar)
The location must not be near heat-generating
equipment or in direct sunlight and protected from
weather.
The location must not obstruct air flow through or
around the ice machine. Refer to chart below for
clearance requirements.
The ice machine must be protected if it will be
subjected to temperatures below 32°F (0°C).
Failure caused by exposure to freezing
temperatures is not covered by the warranty. See
"Removal from Service/Winterization"
Part Number 80-1479-3 7/10

Installation

Warning
!
.
21