Suction Pressure High Checklist - Manitowoc S300 Technician's Handbook

S series
Table of Contents

Advertisement

Suction Pressure High Checklist

Improper Installation
Refer to "Installation/Visual Inspection Checklist"
page 108
Discharge Pressure
Discharge pressure is too high and is affecting low
side – refer to "Freeze Cycle Discharge Pressure
High Checklist" (page 113)
Improper Refrigerant Charge
Overcharged (also see "Freeze Cycle Discharge
Pressure High Checklist" page 113)
Wrong type of refrigerant
Components
Harvest valve leaking - continue the table
Harvest pressure solenoid valve leaking - continue
the table
TXV flooding - continue the table
Defective compressor - continue the table
Other
Non-Manitowoc components in system
116