MAIN FUSE

The main fuse is 250 Volt, 7 amp.

FAN CYCLE CONTROL

(Self-Contained Air-Cooled Models Only)
Model
S300 / S320
S420 / S450
S500 / S600
S850
S1000 / S1200
S1400 / S1600
S1800

HIGH PRESSURE CUTOUT (HPCO) CONTROL

Cut-Out
450 psig ±10
(3103 kPa ±69)
31 bar ±.69
Part Number 80-1479-3 7/10

Specifications

Cut-In (Close)
250 ±5
(1723 kPa ±.34)
(17.23 bar ±.34)
275 psig ±5
(1896 kPa ±34)
(18.96 bar±.34)
(Must be below 300 psig
(2068 kPa 20.68 bar) to reset.)
Cut-Out (Open)
200 ±5
(1517 kPa ±.34)
(15.17 bar ±.34)
225 psig ±5
(1551 kPa ±34)
(15.51 bar ±.34)
Cut-In
Automatic Reset
185