HARVEST CYCLE CIRCUITRY

The water level probe does not control the water inlet
valve during the harvest cycle. During the harvest
cycle water purge, the water inlet valve energizes and
de-energizes strictly by time. The harvest water purge
may be set at 45 seconds (top and center terminals) or
0 seconds (center and bottom terminals). Set the
harvest water purge to 0 seconds when reverse
osmosis or deionized water is used. Use the factory
setting of 45 seconds for all other types of water.