Zero-Servo Function - Omron VARISPEED G7 Instruction Manual

Hide thumbs Also See for VARISPEED G7:
Table of Contents

Advertisement

Related Constants
Con-
stant
Number
b7-01
b7-02
Setting Precautions
Droop control is disabled if b7-01 is set to 0.0.
Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
the rated torque is generated.
Constant b7-02 is used to adjust the responsiveness of droop control. Increase this setting if oscillation or
hunting occur.
Setting the Droop Control Gain
Set the droop control gain as the speed reduction at a 100% motor torque, as a percentage of the maximum
output frequency.

Zero-servo Function

The zero-servo function holds the motor when the motor is stopped in what is call a zero-servo status. This
function can be used to stop the motor even with an external force acts on the motor or the analog reference
input is offset.
-128
6
Name
Description
Display
Droop control
Sets the slip as a percentage of
gain
maximum frequency when the
maximum output frequency is
specified and the rated torque
occurs.
Droop Quantity
Droop-control is not performed
when the setting is 0.0.
Droop control
Droop control responsiveness
delay time
constant
When hunting or oscillation
Droop Delay
occurs, increase the value.
Time
Torque
0
Fig 6.73 Droop Control Gain
Change
Setting
Factory
during
Range
Setting
Opera-
tion
0.0 to
0.0
Yes
100.0
0.03 to
0.05 s
No
2.00
b7-01
Speed reference
Control Methods
Open
V/f
Flux
Loop
V/f
with
Vec-
Vector
PG
tor
1
No
No
No
A
A
A
A
A
100%
Speed
Open
Loop
Vector
2
A
A