Related Constants
Con-
stant
Number
b7-01
b7-02
Setting Precautions
Droop control is disabled if b7-01 is set to 0.0.
•
Set b7-01 to the amount of slip as the percentage of slip when the maximum output frequency is input and
•
the rated torque is generated.
Constant b7-02 is used to adjust the responsiveness of droop control. Increase this setting if oscillation or
•
hunting occur.
Setting the Droop Control Gain
Set the droop control gain as the speed reduction at a 100% motor torque, as a percentage of the maximum
output frequency.
Zero-servo Function
The zero-servo function holds the motor when the motor is stopped in what is call a zero-servo status. This
function can be used to stop the motor even with an external force acts on the motor or the analog reference
input is offset.
-128
6
Name
Description
Display
Droop control
Sets the slip as a percentage of
gain
maximum frequency when the
maximum output frequency is
specified and the rated torque
occurs.
Droop Quantity
Droop-control is not performed
when the setting is 0.0.
Droop control
Droop control responsiveness
delay time
constant
When hunting or oscillation
Droop Delay
occurs, increase the value.
Time
Torque
0
Fig 6.73 Droop Control Gain
Change
Setting
Factory
during
Range
Setting
Opera-
tion
0.0 to
0.0
Yes
100.0
0.03 to
0.05 s
No
2.00
b7-01
Speed reference
Control Methods
Open
V/f
Flux
Loop
V/f
with
Vec-
Vector
PG
tor
1
No
No
No
A
A
A
A
A
100%
Speed
Open
Loop
Vector
2
A
A