"B" Group: Fine Tuning Functions

3-6-12 Automatic User Parameter Registration

Func.
Code




3-6-13 Torque Limit Function

The automatic user parameter setting function allows you to make the inverter
automatically record changed function codes in  to . You can use the
stored function codes as a history of data change. To enable this function,
select "" (enabling automatic user parameter setting) for the .
When any data is changed and
stored in  to  sequentially.
The latest data is in , and the oldest one is in .
Stored function codes in  to  are not duplicated. If duplicated func-
tion code is changed, old existing function code is deleted. If number of
changed function code exceeds 32, the oldest one in  is deleted.
"B" Function
Name
User parameter automatic
setting function selection
User parameters 1 to 32
Torque limit function allows you to limit the motor output when 03 (SLV) is set
for the V/F characteristics set at parameter . You can select one of the fol-
lowing modes with the torque limit selection ().
1. Quadrant-specific setting mode (=)
In this mode, individual torque limit value to be applied to four quadrants (i.e.
forward powering, reverse regeneration, reverse powering and forward regen-
eration) are set as the torque limits 1 to 4 ( to ), respectively.
2. Terminal-switching mode(=)
In this mode, the torque limit values set in the torque limits 1 to 4 ( to
) are switched from one another according to the combination of the
states of torque limit switch terminals 1 and 2 (TRQ1 and TRQ2) assigned to
intelligent input terminals. A single selected torque limit is valid in all the oper-
ating states.
3. Analog voltage input mode(=)
In this mode, the torque limit value is set by a voltage applied to the control cir-
cuit terminal O. The voltage range 0 to 10V corresponds to the torque limit
value range 0 to 200%. A single selected torque limit is valid in all the operat-
ing states.
If parameter " (TL: whether to enable torque limitation)" has been assigned
to any intelligent input terminal, the torque limit mode selected by the setting
of  is enabled only when the TL terminal is turned ON. When the TL ter-
minal is turned OFF, torque limit settings are invalid, and the maximum torque
setting is applied as a torque limit.
It the TL function has not been assigned to the intelligent input terminal, the
torque limit mode selected by the setting of  is always enabled.
Each torque limit value used for this function is expressed as a ratio of the
maximum torque generated when the inverter outputs its maximum current on
the assumption that the maximum torque is 200%.
Note that each torque limit value does not represent an absolute value of
torque. The actual output torque varies depending on the motor.
key is pressed, the function code will be
Description
Two option codes:

OFF (Disabled)

ON (Enabled)
Set range,
"", ~
Section 3-6
Run
Defaults
Mode
EU
Units
Edit

137