"D" Group: Monitoring Functions
3-3
"D" Group: Monitoring Functions
Func.
Code
Output frequency monitor
Output current monitor
Rotation direction monitor
PID feedback value monitor
Multi-function input monitor
Multi-function output monitor
Output frequency monitor
Real frequency monitor
Torque reference monitor
Torque bias monitor
Output torque monitor
Output voltage monitor
Input power monitor
Integrated power monitor
Total RUN time
74
You can access important parameter values with the "D" Group monitoring
functions, whether the inverter is in Run Mode or Stop Mode. After selecting
the function code number for the parameter you want to monitor, press the
Function key once to show the value on the display. In functions
, the intelligent terminals use individual segments of the display to show
ON/OFF status.
If the inverter display is set to monitor a parameter and powerdown occurs,
the inverter stores the present monitor function setting. For your convenience,
the display automatically returns to the previously monitored parameter upon
the next powerup.
"D" Function
Name
Real time display of output frequency to motor
from 0.00 to 400.00 (Hz) If is set high,
output frequency () can be changed by
up/down key with d001 monitoring.
Filtered display of output current to motor,
range is 0.00 to 9999.00
Three different indications:
"" ...Forward
"" ...Stop
"" ...Reverse
Displays the scaled PID process variable
(feedback) value ( is scale factor), 0.00 to
999000.0
Displays the state of the intelligent input termi-
nals:
Displays the state of the intelligent output ter-
minals:
Displays the output frequency scaled by the
constant in . Decimal point indicates
range: 0.00 to 40000.0
Displays the actual frequency, range is
-400.00 to 400.00
Displays the torque command, range is
-200. to +200.
Displays the torque bias value, range is
-200. to +200.
Displays the output torque, range is -200. to -
+200.
Voltage of output to motor, Range is 0.0 to
600.0
Displays the input power, range is 0.0 to 100.0 –
Displays watt-hour of the inverter, range is 0.0
to 9999000.0
Displays total time the inverter has been in
RUN mode in hours. Range is 0 to 9999 /
1000 to 9999 / 100 to 999 (10,000 to 99,900)
Description
ON
OFF
7
6 5 4
3
2
1
Terminal numbers
ON
OFF
Relay 12 11
Section 3-3
and
Run
Units
Mode
Edit
–
Hz
–
A
–
–
–
-
–
–
–
–
–
-
–
Hz
–
%
–
%
–
%
–
V
KW
–
–
–
hours