Electronic Thermal Characteristic Curve - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

"B" Group: Fine Tuning Functions
Func.
Code

Free setting, electronic thermal
current 2

Free setting, electronic thermal
frequency 3

Free setting, electronic thermal
current 3

E. thermal Dec Mode

E. thermal Dec Time

E. thermal Dec TimeCnst

E. thermal AccmGain
!WARNING
3-6-3-1

Electronic Thermal Characteristic Curve

=
( HD )
Trip time (s)
60
3.0
0
109%
124
"B" Function
Name
Range is 0.00 to rated current
Range is 0.00 to 400.00 Hz
Range is 0 to rated current
00: Off
01: Fixed Linear
02: LinDec Time
03: DecTimeCnst
0.10 to 100000.00
0.10 to 100000.00
1.0 to 200.0
When parameter , level of electronic thermal setting, is set to motor FLA
rating (Full Load Ampere nameplate rating), the inverter provides solid state
motor overload protection at 115% of motor FLA or equivalent. If parameter
 exceeds the motor FLA rating, the motor may overheat and be dam-
aged. Parameter , level of electronic thermal setting, is a variable param-
eter.
• Inverter and motor models are be treat separately:
• E05 error will be reported in case of Motor overload
• E38 error will be reported in case of Inverter overload
• Inverter protection is set to constant torque characteristic and inverter
rated current
The characteristic curve depends on dual rate setting in  as follows.
Percentage of
150%
200%
b012/b212
The characteristic curve is unique, but reduction rate depending on frequency
is selected in .
Run
Mode
Description
Edit
=
( ND )
Trip time (s)
60
0.5
0
116%
120%
Section 3-6
Defaults
EU
Units
0.00
Amps
0.00
Hz
0.00
Amps


s

s

%
Percentage of
150%
b012/b212