Excessive Pid Deviation - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Using Intelligent Output Terminals
4-6-8

Excessive PID deviation

232
The PID loop error is defined as the
magnitude (absolute value) of the dif-
ference between the Setpoint (target
value) and the Process Variable
(actual value). When the error magni-
tude exceeds the preset value for

, the [OD] terminal signal turns
ON. Refer to "PID Loop Operation" on
page 109.
Option
Terminal
Code
Symbol

OD
Excessive
PID
deviation
Valid for inputs:
11, 12, AL0 - AL2

Required settings:
Notes:
• The default difference value is set to 3%. To change this value, change parameter
 (deviation level).
• The example circuit for terminal [11] drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the
inverter's output transistor.
SP, PV
C044
C044
[OD]
1
signal
0
Function
State
Name
ON
when PID error is more than the set
threshold for the deviation signal
OFF
when PID error is less than the set
threshold for the deviation signal
Section 4-6
Process variable
Setpoint
ON
ON
t
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents