User Parameter

Param-
eter
Name
Num-
ber
Initialize Data
Language
selection for
Digital Opera-
A1-00
tor dis-
play(JVOP-
160-OY only)
Parameter
A1-01
access level
Control method
A1-02
selection
A1-03 Initialize
Sequence / Reference Source
Reference
b1-01
source selec-
tion
RUN com-
b1-02
mand source
selection
Stopping
b1-03
method selec-
tion
Prohibition of
b1-04
reverse opera-
tion
Acceleration / Deceleration Settings
Acceleration/
C1-
Deceleration
times
S-Curve Settings
S-curve char-
C2-
acteristic time
at acceleration
EN-18
Description
0:English
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
0:Monitoring only (Monitoring drive
mode and setting A1-01 and A1-04.)
1: Used to select user parameters (Only
parameters set in A2-01 to A2-32 can
be read and set.)
2: Advanced
(Parameters can be read and set in
both, quick programming mode (Q)
and advanced programming mode
(A).
0:V/f control
1: V/f control with PG
2: Open loop vector control
3: Closed loop vector control
0:
No initializing
1110: Initializes using the user
parameters
2220: Initializes using a two-wire
sequence. (Initializes to the
factory setting.)
3330: Initializes using a three-wire
sequence.
Sets the frequency reference input
method.
0:Digital Operator
1: Control circuit terminal (analog input)
2: Serial communication (RS422 / 485)
3: Option Card
Sets the run command input method.
0:Digital Operator
1: Control circuit terminal (digital inputs)
2: Serial communication (RS422 / 485)
3: Option Card
Selects the stopping method when the
Run signal is removed
0:Deceleration to stop
1: Coast to stop
2: DC injection to stop
3: Coast to stop with timer (New Run
commands are disregarded while
coasting.)
0:Reverse enabled
1: Reverse disabled
2: Output Phase Rotation (both rota-
tional directions are enabled)
3: Output Phase Rotation with Reverse
disabled.
Sets the time to accelerate/decelerate
from 0 Hz to the maximum output fre-
quency.
Sets the S-curve characteristic at accel-
eration start and end.
Param-
eter
Name
Num-
ber
Motor Slip Compensation (not available in V/f with
PG)
Used to improve speed accuracy
Slip compensa-
• Increase if output frequency is too low
C3-01
tion gain
• Decrease if output frequency is too
high.
Sets the slip compensation delay time
Slip compensa-
• Increase if output frequency is not
tion delay time
C3-02
stable
(only available
• Decrease setting when slip compen-
in V/f and OLV)
sation responsiveness is low.
Speed Control (ASR) (only available in V/f with PG
and CLV)
ASR propor-
Sets the proportional gain of the speed
C5-01
tional gain 1
loop (ASR)
ASR integral
Sets the integral time of the speed loop
C5-02
time 1
(ASR)
P,I
ASR propor-
C5-03
tional gain 2
ASR integral
C5-04
time 2
0
ASR delay time
C5-06
Sets the ASR filter time constant.
(only CLV)
ASR switching
Sets the frequency for switching
C5-07
frequency
between ASR gain 1, 2 and ASR integral
(only CLV)
time 1, 2
ASR integral
Sets the limit for the integral part of the
C5-08
limit
ASR controller.
(only CLV)
Carrier Frequency
0:Heavy Duty
Heavy/Normal
C6-01
1: Normal Duty 1
duty selection
2: Normal Duty 2
Selects the carrier frequency (factory
setting depends on Inverter capacity)
0: Low noise, low carrier
Carrier fre-
1: 2.0 kHz
2: 5.0 kHz
C6-02
quency selec-
3: 8.0 kHz
tion
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
F: Programmable pattern
Speed Settings
Multi speed
d1-01
to
references 1 to
d1-16
16
Sets the multi-step speed references.
Jog frequency
d1-17
reference
Torque Control (only available in CLV)
Torque control
0:Speed control
d5-01
1: Torque control
selection
Sets the delay from inputting a "speed/
Speed/torque
torque control change" signal (by digital
d5-06
control switch
input) until the control is acutally
over timer
changed
V/f Pattern Settings
Input voltage
This setting is used as a reference value
E1-01
setting
for protection functions.
Description
P = C5-01
I = C5-02
P = C5-03
I = C5-04
Motor
E1-04
speed (Hz)