Using Intelligent Input Terminals
4-5-1

Forward Run/Stop and Reverse Run/Stop Commands:

!WARNING
When you input the Run command via the terminal [FW], the inverter exe-
cutes the Forward Run command (high) or Stop command (low). When you
input the Run command via the terminal [RV], the inverter executes the
Reverse Run command (high) or Stop command (low).
Option
Terminal
Code
Symbol

FW

RV
Valid for inputs:
Required settings:
Notes:
• When the Forward Run and Reverse Run
commands are active at the same time, the
inverter enters the Stop Mode.
• When a terminal associated with either [FW]
or [RV] function is configured for normally
closed, the motor starts rotation when that
terminal is disconnected or otherwise has no
input voltage.

Note The parameter
Run key issues a Run FWD command or Run REV command. However, it has
no effect on the [FW] and [RV] input terminal operation.
If the power is turned ON and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power ON, confirm that the
Run command is not active.
Function
State
Name
Forward
ON
Run/Stop
OFF
Reverse
ON
Run/Stop
OFF
~
 = 
, Keypad Run Key Routing, determines whether the single
Section 4-5
Description
Inverter is in Run Mode, motor runs
forward
Inverter is in Stop Mode, motor
stops
Inverter is in Run Mode, motor runs
reverse
Inverter is in Stop Mode, motor
stops
Example (default input configura-
tion shown – see page 153)
RV FW
7
6
5
4
3
2
1
L
See I/O specs on page 195.
P24
PLC
PCS
205