Fuse Sizes - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Fuse Sizes

7
Fuse Sizes
xxii
The inverter shall be connected with a UL Listed Cartridge Nonrenewable
fuse, rated 600Vac with the current ratings as shown in the table below.
Inverter Model
3G3MX2-AB001,
3G3MX2-AB002,
3G3MX2-AB004
3G3MX2-AB007
3G3MX2-AB015
3G3MX2-AB022
3G3MX2-A2001,
3G3MX2-A2002,
3G3MX2-A2004
3G3MX2-A2007,
3G3MX2-A2015
3G3MX2-A2022
3G3MX2-A2037,
3G3MX2-A2055
3G3MX2-A2075
3G3MX2-A2110,
3G3MX2-A2150
3G3MX2-A4004,
3G3MX2-A4007,
3G3MX2-A4015,
3G3MX2-A4022
3G3MX2-A4030,
3G3MX2-A4040
3G3MX2-A4055,
3G3MX2-A4075
3G3MX2-A4110
3G3MX2-A4150
Type
Class J
10A, AIC 200kA
15A, AIC 200kA
20A, AIC 200kA
30A, AIC 200kA
10A, AIC 200kA
15A, AIC 200kA
20A, AIC 200kA
30A, AIC 200kA
40A, AIC 200kA
80A, AIC 200kA
10A, AIC 200kA
15A, AIC 200kA
20A, AIC 200kA
30A, AIC 200kA
40A, AIC 200kA
7
Rating