Step-by-Step Basic Installation
!WARNING
!Caution Only authorized people should be allowed to open the cover.
!Caution Do not touch the cover during the power supply and for some time after the
2-3-2

Installation Environment clearance

Mounting Orientation and Spacing

Always install the housing in an upright position. Leave 10 cm space above
and below the housing for proper cooling. Leave 10 cm space to the left and
to the right for replacement of the dust filter.

Removing the Front Cover

Turn off the power supply before removing the cover. Not doing so may result
in a serious injury due to an electric shock.
1. Loosen the three screws that hold the front cover.
2. Pull the bottom of the front cover for about 5 cm.
3. Move the front cover upwards to remove.
power shutdown. Doing so might result in a moderate burn.

Mounting MX2 IP54 Mounting Plate

All housings use for M6 mounting screws. Be sure to use lock washers or
other means to ensure screws do not loosen due to a vibration.
50 mm or more
Make sure the ambient temperature remains within the rated range (10 to
50C). Take note that if the ambient temperature reaches or exceeds 40C,
the carrier frequency and output current must be derated (check derating
tables per each inverter model in Derating Curves on page 9). If the Inverter is
used in an environment exceeding the allowable operating temperature range,
the product life of the Inverter (specifically, the capacitor) will be shortened.
Measure and check the temperature approx. 5 cm from the bottom center of
the Inverter body.
Provide sufficient space around the Inverter because it can become very hot
(up to 150C or so). Or provide the right air ventilation forced cooling flow
when designing the enclosure :
100 mm or more
Air flow
Wall
100 mm or more
Section 2-3
Provide sufficient
space so that the top
and bottom wiring
ducts, etc. will not
obstruct the flows of
cooling air.
31