"P" Group: Other Parameters
3-9-7
Speed/positioning switching function (SPD)
3-9-8
Homing function
• Set SPD terminal ON, then speed control is enabled in simple positioning
mode.
• While SPD terminal is ON, current position counter is 0. When SPD is
turned OFF, the inverter starts positioning operation.
• If positioning command data is 0 at SPD turning OFF, the inverter start
deceleration immediately. (Depending on DC braking setting, motor could
be hunting.)
• While SPD terminal is ON, rotating direction depends on RUN command.
Be sure to check rotating direction after switching to positioning operation.
Output Frequency
Speed control
ON
SPD input
Parameter
C001-C007
Multi-function input 1 to
7 selection
• Two different homing function are available by setting homing mode selec-
tion ().
• When trigger signal of homing (: ORG), the inverter starts homing oper-
ation. When homing is completed, current position data is reset (0).
• Direction of homing is specified in .
• If homing is not operated, position at power up is regarded as home posi-
tion (0).
Code
Zero return mode
Zero return direction
selection
Low-speed zero return
frequency
High-speed zero return
frequency
Multi-function input 1 to
7 selection
~
Start position counting
Position control
Item
Data
73
SPD: Speed/position switching
Item
Data or data range
0.00 to 10.00 Hz
0.00 to 50.00 Hz
Section 3-9
Time
Target position
Description
Description
Low speed
High speed 1
FWD (Forward side)
REV (Reverse side)
ORL: Zero return limit
signal
ORG: Zero return
startup signal
187