ModBus mapping
B-5-2
Big/Little endian setup
B-5-2-1
Functional outline
B-5-2-2
Setting parameter
B-5-2-3
Coverage of endian
B-5-2-4
Parameter enable
B-5-2-5
Communication command that can be used by this function
354
It allows to change the message structure of the Modbus, USB and Option
communication.
P400 (Big endian / Little endian selection)
Func. Code
Big/Little endian
selection
Example:
Word Data = 0x0102, Double Word Data = 0x01020304
Word Data / Endian of Word Data:
No.
Big endian
1
01
2
02
Double Word Data / Endian of Double Word Data
No.
Big endian
1
01
2
02
3
03
4
04
Note The software tool will not operate if modified.
Endian is applied only to the register data.
It is not applied to the coil and the register number, etc.
P400: Changes on this parameter becomes effective at power ON or after a
reset.
The list of the communication that can use this function are shown below.
Modbus communication command (RS485, USB)
No.
Modbus function code
1
2
3
4
Name
00: Big endian
01: Little endian
02: Special endian
Little endian
Special endian
02
01
Little endian
Special endian
04
03
02
01
Function name
03h
Read Holding Register
06h
Write Single Register
10h
Write Multiple Registers
17h
Read/Write Multiple Registers
Section B-5
Settings
01
02
03
04
01
02
EU
00