ModBus Data Listing
(iv) List of registers
Register
Function name
No.
1103h
Acceleration time 1
1104h
1105h
Deceleration time 1
1106h
1107h
Operator rotation direction
selection
1108h to
Unused
1200h
(v) List of registers (function modes)
Parameter group A
Register
Function name
No.
1201h
Frequency reference selection
1202h
Run command selection (*)
1203h
Base frequency
1204h
Maximum frequency
1205h
O/OI selection
1206h to
(Reserved)
120Ah
120Bh
O start frequency
120Ch
120Dh
O end frequency
120Eh
120Fh
O start ratio
1210h
O end ratio
1211h
O start selection
1212h
O, O2, OI sampling
1213h
Drive Programming (EzSQ)
selection
1214h
(Reserved)
1215h
Multi-step speed selection
1216h
Multi-step speed reference 0
1217h
1218h
Multi-step speed reference 1
1219h
121Ah
Multi-step speed reference 2
121Bh
121Ch
Multi-step speed reference 3
121Dh
121Eh
Multi-step speed reference 4
121Fh
1220h
Multi-step speed reference 5
1221h
1222h
Multi-step speed reference 6
1223h
1224h
Multi-step speed reference 7
After changing the setting, keep the time 40 ms or longer before actually give run command
324
Function
R/W
Monitoring and setting items
code
F002 (high)
R/W
0 to 360000
F002 (low)
F003 (high)
R/W
0 to 360000
F003 (low)
F004
R/W
00 (forward rotation), 01 (reverse
rotation)
Inaccessible
Function
R/W
Monitoring and setting items
code
A001
R/W
00 (digital operator), 01 (terminal), 02
(operator), 03 (Modbus communica-
tion), 04 (option ), 06 (pulse train fre-
quency), 7 (drive programming),
10 (operation function result)
A002
R/W
01 (terminal), 02 (operator), 03 (Modbus
communication), 04 (option)
A003
R/W
300 to "maximum frequency"
A004
R/W
300 to 4000
A005
R/W
00 (switches between O/OI via terminal
AT), 02 (switches between O/FREQ
adjuster via terminal AT), 03 (switches
between OI/FREQ adjuster via terminal
AT)
A011 (high)
R/W
0 to 40000
A011 (low)
A012 (high)
R/W
0 to 40000
A012 (low)
A013
R/W
0 to "O end ratio"
A014
R/W
"O start ratio" to 100
A015
R/W
00 (start FQ), 01 (0 Hz)
A016
R/W
1 to 30 or 31 (500 ms filter ±0.1 Hz
with hysteresis)
A017
R/W
00 (disable), 01 (PRG start),
02 (always ON)
A019
R/W
00 (binary), 01 (bit)
A020 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A020 (low)
R/W
A021 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A021 (low)
R/W
A022 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A022 (low)
R/W
A023 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A023 (low)
R/W
A024 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A024 (low)
R/W
A025 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A025 (low)
R/W
A026 (high)
R/W
0 or "start frequency" to "maximum
frequency"
A026 (low)
R/W
A027 (high)
R/W
0 or "start frequency" to "maximum
frequency"
Section B-4
Data
resolution
0.01 [sec.]
0.01 [sec.]
Data
resolution
0.1 [Hz]
0.1 [Hz]
0.01 [Hz]
0.01 [Hz]
1 [%]
1 [%]
1
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]

Hide quick links: