Run Signal - Hitachi WJ200 Series Quick Reference Manual

Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Run Signal

When the [RUN] signal is selected as an
intelligent output terminal, the inverter outputs
a signal on that terminal when it is in Run
Mode. The output logic is active low, and is
the open collector type (switch to ground).
Option
Terminal
Code
Symbol
RUN
Run Signal
00
11, 12, AL0 – AL2
Valid for inputs:
(none)
Required settings
Notes:
The inverter outputs the [RUN] signal
whenever the inverter output exceeds the start
frequency specified by parameter B082. The start
frequency is the initial inverter output frequency
when it turns ON.
The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter's output transistor.
Function Name
State
ON
OFF
1
[FW,RV]
0
B082
Output
frequency
Run
signal
Description
when inverter is in Run Mode
when inverter is in Stop Mode
Example for terminal [11] (default output
configuration shown – see
Inverter output
terminal circuit
CM2
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
AL0
Power
supply
See I/O specs on
page 4-6
36
start freq.
ON
page
3-54):
RUN
11
RY
page 4-35 and
3-54):
RUN
AL1
AL2
Load
t

Advertisement

Table of Contents
loading

Table of Contents